V1M
1 pump, 1-ph, up to 18A
Description
Control and protection panel for 1 single-phase pump up to 18A 230VAC
- Supply: 230 VAC
- Admissible voltage range: ±20% > (>30%: auto disconnection)
- Maximum intensity: 18A – AC3
- Overload setting (Amp. max): 1…18A
- Underload adjustment (Min. Amp.): 1…18A
- Overload trip time: 7 s
- Underload trip time: 4 s
- Reset time: 15 minutes (fixed)
- Maximum capacitor capacity: 80 μF (50 μF inside the unit)
- Voltage in probes: 24 VAC
- Sensitivity in probes: 9 KΩ ±15% (fixed)
- Remote connection: Contact or voltage 6…400 VAC/VDC
- Alarm output contact:
- AC1 : 2A / 250 VAC
- AC11 : 1A / 230 VAC
- Control connection: 4 mm² terminal blocks
- Mounting: Wall, with clamps
- Size/Weight/IP/Temperature: 200 x 150 x 80 mm / 850 g / IP56 / -10º…+55º C
Codes and references
10002969 | V1M |
---|