V2T-30
SPD, tYPE 2, 1P+N 30kA
Description
Protector against overvoltage transitory, caused by atmospheric discharges, switching operations in electric circuits and electrostatic discharges.
The equipment incorporates protection with GAS discharge to avoid possible current leakage to earth due to varistor wear.
Avoid the damage that these transient overvoltages may cause to the equipment that is fed from the network.
This equipment DOES NOT PROTECT against voltage surges.
SPECIFICATIONS | strong>Values |
---|---|
230 VAC | |
Maximum voltage Uc | 320 VAC |
Frequency | 50-60 Hz |
≤1,5 kV | |
Maximum discharge intensity ((8/20μs) Imax | 30 kA |
Nominal intensity (8/20μs) In | 15 kA |
Maximum cable section in terminals | 16 mm² |
100 A gL | |
Dimensions (width x height x depth) mm | 18 x 90 x 71 |
Assembly | Rail DIN 35 |
Product standards | IEC 61643-11 / EN61643-11 |
Class | II |
Temperature ranges | -40º… +80º C |
Window | |
Average weight approx. | 140 g |
No. of DIN modules | 1 |
Codes and references
10001750 | V2T-30 – 1P+N 30kA |
---|---|
10002089 | Módulo de repuesto / Replacement module V2T-30 |