V2T-50/100
Transitoria, monofásico, Clase I+II
Description
Protection against overvoltage caused by atmospheric discharges, switching operations in electrical circuits and electrostatic discharges in single-phase installations.
The equipment incorporates protection with GAS discharge to avoid possible current leakage to earth due to varistor wear.
This equipment DOES NOT PROTECT against voltage surges.
SPECIFICATIONS | strong>Values |
---|---|
240 VAC | |
Maximum voltage Uc | 385 VAC |
Frequency | 50-60 Hz |
≤1,8 kV (PE/N) ≤ 1,8 kV (L/N) | |
Impulse intensity (10/350μs) Iimp | 100 kA (PEN/N) 50 kA (L/N) |
Maximum discharge intensity ((8/20μs) Imax | 100 kA |
Nominal intensity (8/20μs) In | 50 kA |
Maximum cable section in terminals | 35 mm² |
500 A gL | |
Dimensions (width x height x depth) mm | 72 x 94 x 71 |
Assembly | Rail DIN 35 |
Product standards | IEC 61643-11 / EN61643-11 |
Class | I+II |
Temperature ranges | -40º… +80º C |
Window | |
Average weight approx. | 290 g |
No. of DIN modules | 4 |
Codes and references
10002490 | V2T-50/100 |
---|