V3T-50/100
Transitoria, trifásica, Clase I+II
Description
Surge protector designed for lines where the risk of direct discharge of lightning is high, in three-phase installations.
It is installed in the meter area or in the switchboard of the house, in parallel with the supply network, so that the service current does not pass through the equipment.
Suitable for use in installations without space for a separate Class I and Class II module.
This equipment DOES NOT PROTECT against power surges.
SPECIFICATIONS>/th> | strong>Values |
---|---|
240 VAC | |
Maximum voltage Uc | 385 VAC |
Frequency | 50-60 Hz |
≤1,8 kV (PE/N) ≤1,8 kV (L/N) | |
Impulse intensity (10/350μs) Iimp | 100 kA (PE/N) 50 kA (L/N) |
Maximum discharge intensity ((8/20μs) Imax | 100 kA |
Nominal intensity (8/20μs) In | 50 kA |
Maximum cable section in terminals | 35 mm² |
500 A gL | |
Dimensions (width x height x depth) mm | 144 x 94 x 71 |
Assembly | Rail DIN 35 |
Product standards | IEC 61643-11 / EN61643-11 |
Class | I+II |
Temperature ranges | -40º… +80º C |
Window | |
Average weight approx. | 660 g |
No. of DIN modules | 8 |
Codes and references
10002489 | V3T-50/100 |
---|